SA5502-IX dual-channel online acid/alkali concentration meter
Overview
SA5502-IXdual-channel online acid/alkali concentration meter, can connect two concentrationelectrode, HCL or NaOHperform measurement, one channel can be set as HCL, the other channel is NaOH, both channels can also be set as HCLor NaOH.
SA5502-IXwith full display, menu-driven operation, fully intelligent, Functions, measurementhigh performance, and strong environmental adaptability Features.
widely used in thermal power, chemical and other industries, suitable for checking high-purity water from ion exchangepure waterregeneration liquor in the processconcentration, orused to prepare boiler, pipeline pickling liquor, acid in liquor, concentration continuous monitoring.
Technical specifications
- Measuring range: concentration: (0.00–10.00)%HCL, (0.00–10.00)%NaOH, temperature: 0–99.9℃;
- Electronic unit basic error: concentration: ±1.0%, temperature: ±0.3℃;
- Automatic temperature compensation range: 0–99.9℃;
- measured solution: 0–99.9℃, 0.6MPa;
- Instrument basic error: concentration: ±2.0%(after calibration at common pointserrorcan be less than 0.1%), temperature: ±0.5℃(0.0℃≤T≤60.0℃);
- Electronic unit repeatability error: ± 1.0%;
- electronic unit Stability: ±1.0% /24h;
- current Isolated output: 4–20 mA(load<750Ω );
- Output current error: ≤±1%FS;
- temperaturecoefficient compensation range:(0–10.0)%/℃(adjustable);
- the two channels are independent, without mutual interference.
- channel 1 is HCL, channel 2 is NaOH;
- simultaneouslymeasurement, on the same screendisplay
- Power supply: AC220V±22V, 50Hz±1Hz; optionalDC24±2.4V,1Apower supply;
- Ingress protection: IP65;
- data retention after power loss:10 years;
- Overall dimensions: 146 (L)×146 (W)×108 (D)mm,Cutout size: 138×138 mm;
- Weight: 0.8kg;
- Operating conditions: Ambient temperature0–60℃, Relative humidity<85%
- transmitter mounting: cutout/wall-mount;
- electrode Mounting: recommendedflow-throughinstallation.
Standard configuration
| SA5502-Iinstrument | one |
| SA-30sensor | two |
| instruction manual | one |
| certificate of conformity | one copy of |
| flow cell | two |
Features
- fast sensor response;
- sensor measurement Stability;
- high sensor measurement accuracy;
- microprocessor-based, uses high-performanceCPUchip, AccuracyADconversion technology and SMTSMT technology;
- EMC(EMC/RFI)design: designed to European StandardEN50081/50082design and manufacture;
- dustproof and waterproofdesign.